IEC61131 User and Reference Manual
April 22, 2008
152
aout2pt
Generic 2 point AOUT module
Description
The aout2pt I/O module provides two I/O channels for Generic 2 Point Analog output
hardware. Data for each of the I/O channels may be connected to user-defined variables
with the I/O connection editor. The analog outputs are updated continuously with data read
from the variables.
Set the aout2pt module_address to match the address switches on the Generic 2 Point
Analog output hardware.
The aout2pt I/O module may be used in place of any other 2-point analog output-type
module. The aout2pt module type is a useful selection early on in the system design stage
before the final selection of the specific analog output module is known.
I/O Connection
Module address
This module is assigned a unique module address between 0
and 15. No other analog output-type module may use this
module address.
Library type
IO board
Data type
Integer / real
Channel type
Output
Number of channels
2