Control Microsystems 5901 Manual de usuario Pagina 197

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 620
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 196
IEC61131 User and Reference Manual
April 22, 2008
189
DIN channel 14 returns measurement status for AIN channel 3.
OFF = channel 0 data is in range.
ON = channel 0 data is in out of range.
DIN channel 15 returns the measurement type for AIN channel 3.
OFF = channel 0 RTD is using 3-wire measurement.
ON = channel 0 RTD is using 4-wire measurement.
DIN channel 16 is reserved for future use.
I/O Connection
Module address
This module is assigned a unique module address between 0
and 15. No other analog input-type module may use this module
address.
Library type
IO complex equipment
AIN sub-module
Data type
Real
Channel type
Input
Number of channels
8
DIN sub-module
Data type
Boolean
Channel type
Input
Number of channels
16
Vista de pagina 196
1 2 ... 192 193 194 195 196 197 198 199 200 201 202 ... 619 620

Comentarios a estos manuales

Sin comentarios