IEC61131 User and Reference Manual
April 22, 2008
getmtpi2
Get Modbus/TCP Interface method 2
The getmtpi2 function is used to obtain the protocol interface settings used by all Modbus IP
protocols on the specified communication interface. This function supports Enron Modbus
parameters. This function block is used by the SCADAPack 330, SCADAPack 350 and
SCADAPack 32 controller series only.
Arguments
Communication interface to get protocol settings.
100 = Ethernet1
Modbus station number.
1 to 255 in standard Modbus
1 to 65534 in extended Modbus
Modbus addressing mode
0 = standard
1 = extended
Modbus Store and forward enable
Enable store and forward when set to TRUE.
Disable store and forward when set to FALSE.
Enron Modbus enable
Enable Enron Modbus when set to TRUE.
Disables Enron Modbus when set to FALSE.
Enron Modbus station number
1 to 255 in standard Modbus
1 to 65534 in extended Modbus
TRUE when operation is successful.
FALSE when ifType is invalid. Operation is
unsuccessful.