IEC61131 User and Reference Manual
April 22, 2008
setprot2
Set protocol settings method 2
Description
The setprot2 function sets the protocol settings for a specific serial port. This function
supports Enron Modbus parameters.
Use this function only when protocol settings need to be changed within a program. It is
more convenient to use the Controller Serial Ports Settings dialog to download protocol
settings with the program.
Arguments
Sets the protocol settings for the serial port when TRUE.
Set this input to FALSE once the protocol settings have
been set.
Communication port to set port protocol settings. Valid
values are 1 to 4.
Protocol type
0 = none
1 = Modbus RTU
2 = Modbus ASCII
3 = DF1 Full Duplex BCC
4 = DF1 Full Duplex CRC
5 = DF1 Half Duplex BCC
6 = DF1 Half Duplex CRC
7 = DNP
Default = 1
Protocol station number
1 to 255 in standard Modbus
1 to 65534 in extended Modbus
0 to 254 in DF1
Default = 1